26 – APPLICATION
This menu is designed to host two applications using the MDPlc program.
It will not be possible to use both applications simultaneously.
The 558 Application select parameter in the DRIVE CONFIG menu must be used to select between the two possible
applications.
ADV100 PID HVAC application

REFERENCES

Menu
PAR
Description
11000 Set point sel
Parameter for selecting the PID input reference. If you select PID disabilit [-1] the ramp reference and thus the drive
speed depend on the standard selections in the REFERENCES menu. For the other selections the parameters in
the REFERENCES menu are modified so that the ramp reference corresponds to the value of the PID output [3700]
variable.
If you select Digital Param [0] the PID reference corresponds to the value of parameter 11002 Set point sel. One of
the following values can be set:
-1
Disable PID
0
Digital Param
1600
Analog inp 1X
1650
Analog inp 2X
3700
PID output
3710
Pad 6
3712
Pad 7
3714
Pad 8
3716
Pad 9
3718
Pad 10
3720
Pad 11
3722
Pad 12
3724
Pad 13
3726
Pad 14
3728
Pad 15
3730
Pad 16
4024
FieldbusM->S1
4034
FieldbusM->S2
4044
FieldbusM->S3
4054
FieldbusM->S4
4064
FieldbusM->S5
4074
FieldbusM->S6
4084
FieldbusM->S7
4094
FieldbusM->S8
4104
FieldbusM->S9
4114
FieldbusM->S10
4124
FieldbusM->S11
4134
FieldbusM->S12
4144
FieldbusM->S13
4154
FieldbusM->S14
4164
FieldbusM->S15
4174
FieldbusM->S16
Menu
PAR
Description
11002 Set point val
If parameter 11000 Set point val is set to Digital Param [0] the PID input reference value can be written in this
parameter. For the other selections of parameter 11000 Set point val this parameter displays the value of the cur-
rent reference, scaled according to parameters 11012 Signals full scale and 11014 Signals offset and to the unit of
ADV100 • Functions description and parameters list