output of the master to the Speed ratio src input (selection list L_VREF) of the slave drives. The master => slave
connection can be achieved via analog signals or fieldbus.
To ensure correct operation of the Powerloss function, the following alarms must be configured as described below:
Since the speed reference and current limit are controlled internally by the Powerloss function, a difference could
occur between the speed reference and motor speed with subsequent activation of the Perd Riferim alarm: to avoid
this, set Par 4552 SpdRefLoss activity = Ignore
During the power failure, the power supply phase loss detection system might not work properly with subsequent
activation of the Phaseloss alarm: to avoid this, set Par 4660 PhLoss activity=Ignore.
Drv enable
Power supply
Vdc
Speed ref
Speed
Speed ref
Powerloss
Next active
Powerloss
Ramp down
Powerloss
Next ratio
Menu
PAR
Description
22.6.1 3400 Powerloss function
This parameter is used to enable the Powerloss function.
0 Disable
1 Enable
If set to 0 the Powerloss function is disabled. The Sottotensione alarm is generated in the event of a power failure.
92
Powerloss
The mains supply is restored while the function is enabled
The drive switches itself off if the power supply is not restored
Detection possible when the external sensor detects
that the mains supply has been restored
Speed
UM
Type
FB BIT
ENUM
PowerLoss_01.vsd
Def
Min
Disable
0
ADV100 • Functions description and parameters list
Max
Acc
Mod
1
ERWZ F__