24.49
4720 Alm autoreset time
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached the
drive is set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu
PAR
Description
24.50
4722 Alm autoreset number
Setting of the maximum number of attempted automatic resets.
ADV100 • Functions description and parameters list
UM
Type
FB BIT
s
FLOAT
UM
Type
FB BIT
UINT16
Def
Min
0
0
Def
Min
20
0
Max
Acc
Mod
60.0
ERW FVS
Max
Acc
Mod
100
ERW FVS