gefran SIEIDrive ADV100 Functions Description And Parameters List page 89

Field oriented vector
Hide thumbs Also See for SIEIDrive ADV100:
Table of Contents

Advertisement

Drive enabled and demagnetising for a time > Par 3376 Vf catch lastref dly
Drive enabled and demagnetising for a time < Par 3376 Vf catch lastref dly
OutFreq
MotorSpd
OutCurr
Par 3366
Waiting for demagnetiz
Menu
PAR
Description
22.5.2 3364 Vf catch start freq
This parameter is used to configure the frequency at which the procedure to capture a motor that is running starts.
This parameter is used if:
First enabling of the drive after power-on
Drive enabled and demagnetising for a time > Par 3376 Vf catch lastref dly
This parameter must be set to a frequency that is higher than the frequency at which the motor is running at the
beginning of the capture procedure. If the conditions are not always identical the maximum frequency or a few Hz
below this must be set. The reference sign setting must be the same as the sign of the frequency at which the motor
is running.
If a frequency value close to the actual frequency is set, the capture time is short. If there is a big difference between
the frequency value setting and the actual frequency, the capture time is longer.
The recommended setting for this parameter is 0 if the function is enabled for use to capture a motor running due to a
temporary disabling of the drive or to capture a motor running in the case of an automatic restart after an alarm; or in
case of enabling after power-on or after prolonged periods of disabling, the motor speed is certainly 0.
Menu
PAR
Description
22.5.3 3366 Vf catch enable dly
This parameter is used to configure the time to wait for demagnetisation of the motor before executing the procedure
to capture the motor that is running. The waiting time for demagnetisation is measured starting from the moment the
drive detects that the conditions are OK to execute the capture procedure. This parameter is useful for automatic
restarts after an alarm.
If the motor flux is not zero when the enable command is sent the drive might generate the Overcurrent alarm.
The value to set depends on the size of the motor. Large motors have a high rotor time constant and therefore re-
quire a long demagnetisation time. Setting a higher value than necessary is not a problem.
ADV100 • Functions description and parameters list
Condition
First enabling of the drive after power-on
Automatic restart after an alarm
Vf control
Par 3368
Search time
Par 3370 P gain
Par 3372 I gain
Speed search
Magnetiz
UM
Type
Hz
FLOAT
Condition
UM
Type
ms
UINT16
Acceleration
SpeedCapture_01.vsd
FB BIT
Def
50.0
FB BIT
Def
1000
Frequency value
Par 3364 Vf catch start freq
Par 3364 Vf catch start freq
Last frequency before disabling the drive
Last frequency before the alarm occurred
Min
Max
-500.0
500.0
Frequency value
Par 3364 Vf catch start freq
Par 3364 Vf catch start freq
Min
Max
10
10000
Acc
Mod
ERWZ V
Acc
Mod
ERWZ V
89