parameters for a source of Null (0) or the value of 6002 for a source of One (1).
Another alternative is to configure the Digital Enable src and Digital Start src sources on the BitX decomp mon
parameters, so that the Modbus or Fieldbus can then write the desired value on the Dig word decomp parameter.
Local n Remote switching is performed with the variable value configured as Loc/Remote src, i.e. it can be a stand-
ard digital input, expansion digital input, Modbus, Fieldbus, Dig Local/Remote.
In the default condition, the associated variable is Dig Local/Remote, which is written by the LOC key from the key-
pad: switching is thus performed by pressing the LOC key.
For safety reasons, Local n Remote switching is only performed with Terminal Enable = 0.
Example 1
With the machine in automatic operating mode, the drive works in Remote -> Digital -> Fieldbus mode.
With the machine in manual operating mode, the drive works in Local -> Terminal -> Standard digital input mode.
If switching from automatic to manual machine operation, the drive must switch between Remote and Local mode. The
switch command must be sent via standard digital input or fieldbus.
Example 2
With the machine controlled from console A, the drive operates in Local -> Terminal -> Standard digital input mode.
With the machine controlled from console B, the drive operates in Remote ->Digital -> Expansion digital input mode.
When switching the control console, the drive must switch between Remote and Local mode. The switch command
must be sent via Standard digital input or Expansion digital input.
This configuration is allowed because the Terminal variables are available in the digital command selection lists.
Menu
PAR
Description
11.1
1000 Commands remote sel
This parameter defines the source of the command signals when the drive is used in the Remote mode.
The Enable command can only be set via hardware, connecting a positive voltage (+24VDC) to terminal 7.
0 Terminals
1 Digital
When the parameter is set to Terminals the source of the Enable cmd mon command is the Enable terminal (9)
and the origin of the Start cmd mon command is configured using the Terminal Start src parameter.
When the parameter is set to Digital the origin of the Enable cmd mon command is configured using the Digital
Enable src parameter and the origin of the Start cmd mon command is configured using the Digital Start src
parameter.
If Digital is set to generate the Enable cmd mon command, as well as the variable associated with Digital Enable
src, the enable hardware command must also be sent to the Enable terminal.
Menu
PAR
Description
11.2
1002 Commands local sel
This parameter defines the source of the command signals when the drive is used in the Local mode.
0 Terminals
2 Keypad
When the parameter is set to Terminals the source of the Enable cmd mon command is the Enable terminal (9)
and the origin of the Start cmd mon command is configured using the Terminal Start src parameter.
When the parameter is set to Keypad the origin of the Enable cmd mon and Start cmd mon commands is the Start
key. When Keypad is set to generate the Enable cmd mon command, as well as the Start key the enable hardware
command must also be sent to the Enable terminal (9).
44
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
Def
Min
Terminals
0
Def
Min
Keypad
0
ADV100 • Functions description and parameters list
Max
Acc
Mod
1
RWZ FVS
Max
Acc
Mod
2