Table 28: Calibration Menu Item - WAGO I/O-SYSTEM 750 Manual

8ao 0-10v/±10v dc, 8-channel analog output module 0...10 v/±10 v
Table of Contents

Advertisement

53
Commissioning

Table 28: Calibration Menu Item

Option
Selection
of the
calibration
method
Voltage [V]
*)
Factory setting
Manual
Version 1.0.0
Description
Enable factory configuration
*)
Factory calibration is enabled and user calibration is disabled.
Enable
Factory calibration is disabled and user calibration is enabled.
factory
configurati
Gain
The Gain value is specified by the manufacturer.
on
Offset The Offset value is specified by the manufacturer.
Enable user calibration
User calibration is enabled and factory calibration is disabled.
You determine the gain and offset value yourself.
*)
User calibration is disabled and factory calibration is enabled.
Enter the Gain value for the user calibration.
Gain
The Gain value changes the gain factor of the voltage value.
Enable
The resolution is 1/8192.
user
The value entered must fall in the value range of 0 ... 63999.
calibration
Enter the Offset value for the user calibration.
The Offset value moves the zero point of the voltage value
Offset
(offset on the y axis).
The resolution is 1 mV per digit.
The value entered must fall in the value range of
−32768 ... 32767.
Display of the process value in volts (V).
This is a 16-bit value.
The process value is read cyclically from the I/O module.
WAGO-I/O-SYSTEM 750
750-597 8AO 0-10V/±10V DC

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o-system 750-597