4
Process Image
Pos: 21 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/Hinweis: Prozessabbildmapping abhängig von FBK/PFC, ohne Status-/Controlbyte @ 6\mod_1256126797251_21.docx @ 43340 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the process data of some I/O modules or their variants in the
process image depends on the fieldbus coupler/controller used. Please take this
information from the section "Fieldbus Specific Design of the Process Data"
included in the description concerning the process image of the corresponding
fieldbus coupler/controller.
Pos: 22 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/Analogausgangsklemmen/Prozessabbild 750-0597 @ 25\mod_1453474509699_21.docx @ 199144 @ 2223344344 @ 1
The 750-597 I/O module provides 1 status byte (8 bit) and 1 data word (16 bit) per
channel.
The digitized process value is output in a data word via the process image of the
fieldbus coupler/controller as output byte "0" (low) and output byte "1" (high).
The process value is displayed at the following resolution:
Signal type „0-10 V": 15 bit (bit B0 ... B14)
Signal type "+/- 10 V": 16 bit (bit B0 ... B15)