en | Appendices
8.2.5

Arming with Automatic Bypass

Points that are not in normal state and therefore prevent arming can be automatically
bypassed for arming. These points are automatically unbypassed again when the system is
next disarmed.
The following settings are required.
Point must be programmed to point type Intrusion (Bypassable) or Intrusion 24h
(Bypassable)
8.2.6

Automatic Arming / Disarming

Control center is located in the secured area
Program two outputs for signaling the armed / disarmed state
Automatic Arming at a Predefined Time
Define arming time
Automatic bypassing of points can be optionally programmed.
Automatic Arming after Disarming
The option Automatic Arming after Disarming for an area must not be set. The procedure
does not comply with the requirements of EN 50131.
Automatic Disarming at a Predefined Time
Define disarming time
8.2.7

Alarm Output via Siren and Communicator

Alarms, trouble events and other events must be output via siren and/or
communicator.
2014.12 | 13 | F.01U.168.332
The maximum number of points that can be bypassed on arming is set under MAP5000 >
Maximum Bypass Count per Area (typically 1 - value range is not specified by the
standard).
The maximum number of times that a point can be bypassed on arming is set under
MAP5000 > Maximum Times A Device Can Be Bypassed (typically 1 - value range is not
specified by the standard).
The permission May Bypass Detectors In Area must be set for the user. User Manager >
Permission Sets > Arm Category
Include new area if not yet present
Include control center if not yet present
Include the area in the scope of the control center: Local Area
Connect one free output in each case with the device LED
Using the wizard, program one output with the behavior item Area Armed and a second
output with the behavior item Area Disarmed.
The signal must be time-limited. Enter a corresponding time (typically 10 sec. / maximum
of 30 seconds) for Activation Duration.
Start the schedule wizard and define the time of arming.
As action, select Arm Area(s) Using Exit Delay.
Program the duration of the acoustic warning signal before arming in the area: Area
Manager > Area > Exit Delay > Normal Delay Time
The option Arm Only If Area Is Ready To Arm must be deactivated.
For requirements, refer to Arming with Automatic Bypass, page 76
Start the schedule wizard and define the time of disarming.
As action, select Disarm Area(s).
Installation Manual
MAP5000
Bosch Sicherheitssysteme GmbH

Advertisement