MAP5000
Program entry / exit route
Exit Point Type
Initial Follower
Follower
Exit
Interrupt
Restart
Table 8.2: Exit Point Types
Not for EN 50131
1)
The type of entry point must be selected for all entry route points
Entry Point Type
Delay 'Normal'
Delay 'Extended'
Follower
Table 8.3: Entry Point Types
Program delayed reporting for all intrusion points of the area
Bosch Sicherheitssysteme GmbH
The value for the entry / exit delay can be adapted if required: Area Manager > Area >
Timing and Delays Normal Entry Delay (typically 45 sec. / at least 30 sec.) Normal Exit
Delay (typically 60 sec.)
Program all points of the entry / exit route to the point type Intrusion
The type of exit point can be optionally selected for exit route points
Behavior
Point without prevention of arming readiness, e.g. PIR that has the
1
control center in the detection area. Important: Point must be in
normal state after exit, otherwise an alarm will be tripped
Point that does not trip an alarm as long as the exit delay is
1
running. Only relevant for option MAP5000 Panel > Armed State At
Exit Delay Start
Door point that must be mandatorily tripped once upon leaving the
area. The option MAP5000 Panel > Unvacated Premises must be
activated
Door point that shortens the running exit delay to 10 sec. (use
recommended)
Point that restarts the exit delay; possible only once during the exit
Behavior
Door point that starts the entry delay with the value 'Normal'
Door point that starts the entry delay with the value 'Extended'
Point that does not trip an alarm as long as the entry delay is
running
For all points of the point type Intrusion and Intrusion 24h, the parameter Supports
Delayed Reporting must be set to Yes.
For reporting (Event Manager > Panel Event Groups > Properties > Reportable Events),
a Transmission Delay that is the same as the exit delay (typically 45 sec. / at least 30
sec.) must be set for External Intrusion Alarm.
Installation Manual
Appendices | en
75
2014.12 | 13 | F.01U.168.332