en | Cable Connections
3.1.1

Internal/External Data Bus

The MAP 5000 system contains two data buses (BDB), which are used for connection of the
system modules to the ICP-MAP5000 Main Panel.
The Internal BDB may have a maximum length of 3 m and is used for connection of the main
panels in the control panel enclosure (Figure 3.1 Data Bus Connections of the System Modules
on the Internal BDB, page 39).
The external BDB may have a maximum length of 1000 m from the main panel and is used for
connection of the system modules in remote operation.
(Section Figure 3.4 Data Bus Connection of the Control Center on the External BDB, page 41).
Requirements for data bus wiring
No special requirements with respect to
The minimum wire diameter is determined on the basis of the required cable length
The following modules can be operated on the BDB:
Table 3.2
System module
DE Module (ICP-MAP0007)
LSN Gateway (ICP-MAP0010)
Power Supply (IPP-MAP0005)
Control Center (IUI-MAP0001)
When one or more LSN Gateways are operated remotely, there must be one power supply
1
(IPP-MAP0005) installed in the same enclosure.
The following applies for VdS: Control centers for different areas must not be connected on
2
the same BDB.
3.1.2

Topology of the External Data Bus

The External BDB may only be mounted as shown in figure 3.3. Every other bus topology
doesn't conform to the specifications of the BDB.
Figure 3.3 Bus wiring without consideration of the power supply
2014.12 | 13 | F.01U.168.332
Solid or stranded
Twisted or untwisted
Shielded or unshielded
0.6 mm up to 450 m
0.8 mm up to 750 m
1.0 mm up to 1000 m
Internal BDB
X
X
X
X
2
Max. 1000m
Installation Manual
MAP5000
External BDB
X
1
X
X
2
R
= 120 Ohm
E