Venting

Installation into existing adjacent chimney

Note: Co-linear portion of vent system may only be
installed within a solid-fuel burning fi replace and
chimney.
The appliance can be adapted to co-linear applications
using an existing chimney. The appliance must not be
connected to a chimney fl ue serving a separate solid-
fuel burning appliance.
Requires the Co-Axial to Co-Linear appliance Adapter
46DVA-34CLAA or equivalent, two lengths of 2-ply
fl exible chimney liner both approved for venting gas
appliances: one 3" diameter liner for intake and one 4"
diameter liner for exhaust, a 3 x 4 co-linear termination
kit and fl ashing.
The appliance must be fully enclosed while maintaining
clearances to combustibles detailed elsewhere in this
manual.
4" exhaust
3" intake
liner
liner
3" min. bend radius
for intake liner and
4" min. bend radius
for exhaust liner
or 46DVA-GCL34
Clearances
Framed
to combustible
wall
materials listed
elsewhere in this
manual apply
Engine
Installation using 46DVA-34CLAA
Approved 3 x 4
co-linear termination
Flashing
46DVA-34CLAA
Co-linear
adapter
1 x 3"
intake
liner
and
1 x 4"
exhaust
liner
Co-Linear Conversion
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Not required when using co-linear venting.
Note: Co-linear fl exible aluminum venting should be
professionally inspected periodically for corrosion
and damage and replaced when necessary. If the
installation does not allow for future inspection or
replacement of the fl exible aluminum venting, then
stainless steel vent liners should be used.
4" exhaust
3" intake
liner
liner
3" min. bend radius
for intake liner and
4" min. bend radius
for exhaust liner
46DVA-GCL34
or 46DVA-34CLAA
Clearances
Framed
to combustible
wall
materials listed
elsewhere in this
manual apply
Installation using 46DVA-GCL34
Approved 3 x 4
co-linear termination
Flashing
Co-linear
adapter
Max. 12"
1 x 3" intake liner
and
1 x 4" exhaust liner
Engine
27