Co-Linear With Chimney - Valor 1000JN Installation Manual

Direct vent zero clearance gas fireplace
Table of Contents

Advertisement

Venting
Conversion to Co-Linear Liners with a
Chimney
Note: Co-linear liners must only be installed within
a solid fuel burning fi replace and chimney when
converting at unit.
The appliance can be adapted to co-linear applications
using an existing chimney. The appliance must not be
connected to a chimney fl ue serving a separate solid-fuel
burning appliance.
This requires an approved Co-Axial to Co-Linear
appliance adapter, two lengths of 2-ply, 3" diameter
fl exible chimney liners approved for venting gas
appliances, a co-linear termination kit and fl ashing
or a co-linear to co-axial adapter and either a high
wind vertical vent terminal cap or a low profi le vertical
termination.
The appliance should be installed within a fully framed
wall cavity, consistent with a New Construction
application as described in this document.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictors are not required when using co-linear vent-
ing.
Note: Co-linear fl exible aluminum venting
should be professionally inspected periodically
for corrosion and damage and replaced when
necessary. If the installation does not allow for
future inspection or replacement of the fl exible
aluminum venting, then stainless steel vent liners
should be used.
28

Co-linear with Chimney

Co-Linear installation using nearby/adjacent existing chimney -
Conversion at chimney
Any fi nishes
applied above
the fi replace's
opening must
be non-
combustible.
Listed clearances
to combustible
materials apply.
Framed
Wall
Approved
3x3 co-linear
termination
Flashing
2 x 3" liners
3" minimum
bending
radius
46DVA-CLAA,
46DVA-GCL
or equivalent
co-linear
adapter