3. Commissioning
Module parameters: Monitoring of CPX module CPX−CP interface
Function no.
4828 + m * 64 + 0
Description
Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following:
The fault is:
Monitoring
Bit
Description
0
Short circuit/overload in sensor supply (SCS)
1
Short circuit/overload at outputs (SCO)
Values
1 = active (presetting)
0 = inactive
Note
Monitoring can also be set for the complete CPX terminal
(see Monitoring system parameters").
1)
Only effective for CP modules with extended functions
Tab. 3/5:
Monitoring of CPX terminal CPX−CP interface
Module parameters: Monitoring of CPX module CPX−CP interface and CP modules
Function no.
4828 + m * 64 + 6
Description
See Tab. 3/5
Monitoring
Bit
Description
0
CP communication fault (fault 34, 36)
1
CP configuration fault (fault 35)
2
CP modules: Load supply outputs Vout
3
CP modules: Load supply valves Vval
4
CP modules: Load supply sensors Vsen
Values
1 = active (presetting)
0 = inactive
Note
See Tab. 3/5
Tab. 3/6:
Monitoring of CPX module CPX−CP interface and CP modules
Festo P.BE−CPX−CP−EN en 0405NH
Description of the module parameters
sent to the CPX field bus node
shown on the module common fault LED.
m = module number (0 ... 47)
1)
m = module number (0 ... 47)
[Monitor]
[Monitor SCS]
[Monitor SCO]
[Active]
[Inactive]
[Monitor]
[Monitor CAN comm.]
[Monitor config]
[Monitor Vout]
[Monitor Vval]
[Monitor Vsen]
[Active]
[Inactive]