Siemens SINUMERIK 840DE sl Commissioning Manual page 1673

Basesoftware and operating software
Hide thumbs Also See for SINUMERIK 840DE sl:
Table of Contents

Advertisement

Section
Settings
[processing_
StartState=
systemphase]
scanSetupDirs=
scanRemovableDrive
SetupDirs=
scanNetworkDrive
SetupDirs=
numberOfScanCycles
waitTimeBetween
ScanCycles
report
InfoLevel
PCU Base Software (IM10)
Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1
Installing and configuring updates and automation software
Description
Specifies whether the PCU Installer is active during operation of the Desktop.
Possible values:
PCU Installer starts setups
activated
PCU Installer is stopped completely
stopped
You can define exceptions in Section "[noactivation]".
Specifies whether setup directories are to be checked and, if required, setup files
executed during Desktop operation.
The following directories are checked if this setting has been activated:
Local setup directories from the [local_setupdirs] setting are always checked.
You can define separately whether additional directories on removable disks or
in the network are to be checked. (See settings "scanRemovableDriveSetupDirs"
and "scanNetworkDriveSetupDirs")
If you deactivate this setting, neither local directories, nor directories on removable
disks or in the network are checked, i.e. the setting scanSetupDirs=no overwrites, for
example, scanNetworkDriveSetupDirs=yes.
Possible values: yes; no
Specifies whether directories on removable disks are to be checked from the setting
[removable_setupdirs] and, if required, setup files executed during Desktop operation.
The setting "scanSetupDirs" must also be activated so that these directories are
checked.
Possible values: yes; no
Specifies whether network directories are to be checked from the setting [net_setup‐
dirs] and, if required, setup files executed during Desktop operation.
The setting "scanSetupDirs" must also be activated so that these directories are
checked.
Possible values: yes; no
Specifies whether and how often the setup directories check for new setup packages.
Possible values:
Infinite
infinite
Integer
You can define the waiting time between checks in key
waitTimeBetweenScanCycles
Specifies how long the PCU Installer waits after the setup directories have been
checked before checking them again.
Enter the waiting time in milliseconds.
In key numberOfScanCycles, you can specify how often the setup directories will
be checked.
Specifies how detailed the information is to be which is stored in the log files.
Possible values:
1: Only basic information on the actions of the PCU Installer is logged
2: All PCU Installer-specific information is logged
3: All PCU Installer-specific information and some trace information is logged
4: All PCU Installer-specific information and additional trace information is logged
5: All PCU Installer-specific information and all trace information is logged
5.9 PCU Installer
115