Digital Signals; Digital Inputs I1:1 - I1:8 (X10) - Pilz PMCprimo Drive2 Installation Manual

Motion control pmc
Table of Contents

Advertisement

9 Interfaces
9.7

Digital signals

9.7.1

Digital inputs I1:1 - I1:8 (X10)

All digital inputs are electrically isolated through optocouplers
Reference ground is EGND (terminal X10, Pin 2)
Logic is PLC compatible
H-level: +11..24V / 10 mA
L-level: 0 V .. 11 V/ 0 mA
The inputs I1:1 to I1:4 are „fast" inputs (< 1 us) for e.g. product referencing
I1:1 and I1:2 will be additionally mapped to both inputs E2:7 and E2:8