Regen Circuit - Pilz PMCprimo Drive2 Installation Manual

Motion control pmc
Table of Contents

Advertisement

7 General
7.12

Regen circuit

During braking with the aid of the motor, energy is fed back to the PMCprimo Drive2. This energy is
converted into heat in the regen resistor. The regen circuit (thresholds) are adjusted to the supply
voltage with the help of the setup software PDRIVE.
Our applications department can help you with the calculation of the regen power which is required.
A description of the interface can be found on page 50 .
Internal regen resistor:
External regen resistor:
Functional description:
1. Individual amplifiers, not coupled through the DC-link (DC+, DC-)
The circuit starts to respond at a DC-link voltage of 400V, 720V or 840V (depending on the supply
voltage). If the energy which is fed back from the motor, as an average over time or as a peak
value, is higher than the preset regen power, then the PMCprimo Drive2 will output the status
"regen power exceeded" and the regen circuit will be switched off. At the next internal check of the
DC-link voltage (after a few ms) an overvoltage will be detected and the PMCprimo Drive2 will be
switched off with the error message "Overvoltage" (⇒ page 82).
BTB/RTO contact (terminal X3, Pin2+3) will be opened at the same time (⇒page 64)
2. Several servo amplifiers coupled through the DC-link circuit (DC+, DC-)
Thanks to the built-in regen circuit with its patented w-characteristic, several amplifiers (even with
different current ratings) can be operated off a common DC-link, if they have a common supply
voltage. This is achieved by an automatic adjustment of the regen thresholds (which vary, because
of tolerances). The regen energy is distributed equally among all the amplifiers. The combined
power of all the amplifiers is always available, as continuous or peak power. The switch-off takes
place as described under 1. (above) for the PMCprimo Drive2 with the lowest switch-off threshold
(resulting from tolerances). The RTO (BTB) contact of this amplifier (terminals X3, Pin2+3) will be
opened at the same time (⇒ S. 64).
Regen circuit: technical data
Supply voltage
3 x 230 V
3 x 400 V
3 x 480 V
Installation manual PMCprimo Drive2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
PMCprimo Drive2 sz. 01/03
PMCprimo Drive2 sz. 06-20
PMCprimo Drive2 sz. 01-20
Rated data
Upper switch-on level of regen circuit
Switch-off level of regen circuit
Continuous power of regen circuit (RBint)
Continuous power of regen circuit (RBext) max.
Pulse power, internal (RBint max. 1s)
Pulse power, external (RBext max. 1s)
Upper switch-on level of regen circuit
Switch-off level of regen circuit
Continuous power of regen circuit (RBint)
Continuous power of regen circuit (RBext) max.
Pulse power, internal (RBint max. 1s)
Pulse power, external (RBext max. 1s)
Upper switch-on level of regen circuit
Switch-off level of regen circuit
Continuous power of regen circuit (RBint)
Continuous power of regen circuit (RBext) max.
Pulse power, internal (RBint max. 1s)
Pulse power, external (RBext max. 1s)
66 Ohm
33 Ohm
33 Ohm
PMCprimo D
rive2
DIM
01 - 03
06 - 20
V
400 – 430
V
380 – 410
W
80
200
kW
0,25
0,75
kW
2,5
5
kW
5
V
720 – 750
V
680 – 710
W
80
200
kW
0,4
1,2
kW
8
16
kW
16
V
840 – 870
V
800 – 830
W
80
200
kW
0,5
1,5
kW
10,5
21
kW
21
Page 25