Changing Overtorque And Undertorque Detection Levels Using An Analog Input - YASKAWA CIMR-ACA4011 Instruction Manual

Varispeed ac, matrix converter for environmentally friendly motor drives
Table of Contents

Advertisement

Undertorque Detection
Undertorque detection 1 NO
or Undertorque detection 2 NO
Changing Overtorque and Undertorque Detection Levels Using an Ana-
log Input
If parameter H3-09 (Terminal A2 Function Selection) or H3-05 (Terminal A3 Function Selection) is set to 7
(overtorque/undertorque detection level), the overtorque/undertorque detection level can be changed.
If the overtorque/undertorque detection level is changed using the multi-function analog input, only over-
torque/undertorque detection level 1 will be enabled.
The following diagram shows the overtorque/undertorque detection level using an analog input.
Multi-Function Analog Input (H3-05, H3-09)
Set
Value
7
-50
6
Motor current (output torque)
L6-02 or L6-05
L6-03
or
L6-06
The undertorque detection disabled margin is approximately 10% of the MxC rated output
current (or motor rated torque)
Detection level
100%
0
(4 mA)
Fig 6.38 Overtorque/Undertorque Detection Level Using an Analog Input
Function
Overtorque/undertorque detection level
*
L6-03
or
L6-06
on
Multi-function analog input
terminal A2, A3 input level
10 V
(20 mA)
Contents (100%)
Motor rated torque for vector control
MxC rated output current for V/f control
on
Control Methods
Open
Flux
V/f
Loop
Vector
Vector
Yes
Yes
Yes