H4: Multi-Function Analog Outputs
Name
Parameter
Number
Display
Terminal FM
Sets the number of the monitor item to be
Monitor Selection
output (U1-
Items that can be set differ in accordance
H4-01
with the selected control modes.
For information on the parameters for
Terminal FM Sel
which analog output is possible, refer to
U: Monitors.
Terminal FM
Sets the multi-function analog output 1
Gain Setting
voltage level gain.
Sets whether the monitor item output will
be output in multiples of 10 V.
H4-02
Terminal FM
The maximum output from the terminal is
Gain
10 V.
A meter calibration function is available.
Terminal FM Bias
Sets the multi-function analog output 1
Setting
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
H4-03
The maximum output from the terminal is
Terminal FM Bias
10 V.
A meter calibration function is available.
Terminal AM
Sets the number of the monitor item to be
Monitor Selection
output (U1-
Items that can be set differ in accordance
H4-04
with the selected control modes.
For information on the parameters for
Terminal AM Sel
which analog output is possible, refer to
U: Monitors.
Terminal AM
Set the voltage level gain for multi-func-
Gain Setting
tion analog output 2.
Set the number of multiples of 10 V to be
output as the 100% output for the monitor
H4-05
Terminal AM
items. The maximum output from the ter-
Gain
minal is 10 V.
A meter calibration function is available.
Terminal AM
Sets the multi-function analog output 2
Bias Setting
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
H4-06
Terminal AM
The maximum output from the terminal is
Bias
10 V.
A meter calibration function is available.
Terminal FM Sig-
Sets the signal output level for multi-
nal Level Selec-
function output 1 (terminal FM)
H4-07
tion
0: -10 to 10 VDC output
1: -10 to 10 VDC output
AO Level Select 1
Terminal AM Sig-
Sets the signal output level for multi-
nal Level Selec-
function output 2 (terminal AM)
H4-08
tion
0: 0 to +10 VDC output
1: 0 to ±10 VDC output
AO Level Select 2
* The FM output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.
The AM output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
Setting
Description
Range
) from terminal FM.
1 to 99
0.00 to
2.50
*
-10.0 to
+10.0
*
) from terminal AM.
1 to 99
0.00 to
2.50
*
-10.0 to
+10.0
*
0 or 1
0 or 1
Control
Methods
Change
Default
during
Open
Flux
Run
V/f
Loop
Vector
Vector
2
No
A
A
A
1.00
Yes
Q
Q
Q
0.0%
Yes
A
A
A
3
No
A
A
A
0.50
Yes
Q
Q
Q
0.0%
Yes
A
A
A
0
No
A
A
A
0
No
A
A
A
Parameter Tables
MEMO-
BUS
Page
Register
41DH
6-79
4-5
41EH
6-79
41FH
6-79
420H
6-79
4-5
421H
6-79
422H
6-79
423H
6-79
424H
-
41
5-