Storing MxC Set Values in the Digital Operator (READ)
To store MxC set values in the digital operator, follow the directions below.
Step
Digital Operator Display
No.
-ADV-
** Main Menu **
1
Programming
-ADV-
Initialization
2
A1
- 00=1
Select Language
-ADV-
COPY Function
3
o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Funtion Sel
4
o3-01=
0
*0*
COPY SELECT
-ADV-
Copy Funtion Sel
5
o3-01=
1
*0*
MxC→OP READ
-ADV-
READ
6
MxC→OP READING
-ADV-
READ
7
READ COMPLETE
-ADV-
Copy Funtion Sel
8
o3 - 01=0
*0*
COPY SELECT
An error may occur while saving to memory. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display.
Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using the Digital Oper-
ator Copy Function.)
Error Display
PRE
READ IMPOSSIBLE
IFE
READ DATA ERROR
Table 6.1 READ Function Procedure
Press the MENU key, and select Advanced Programming Mode.
Press the DATA/ENTER key, and select the parameters monitor display.
Display o3-01 (Copy Function Selection) using the up arrow key and down arrow
key.
Press the DATA/ENTER key, and select the parameters setting display.
Change the set value to 1 using the up arrow key.
Set the changed data using the DATA/ENTER key. The READ function will start.
If the Read function ends normally, "READ COMPLETE" appears on the digital
operator screen.
The display returns to o3-01 when a key is pressed.
You are attempting to set o3-01 to 1 while o3-02 is set to 0.
Read data length mismatch or read data error.
Digital Operator Functions
Explanation
Meaning
129
6-