Periodic Maintenance of Parts

The MxC is configured of various components, all of which must be operating properly in order to take full
advantage of the MxC functions.
Some electrical components will require maintenance depending on storage conditions and how the MxC is
used. In order to keep the MxC operating normally over a long period of time, it is necessary to perform period
inspections and replace parts according to their service life.
Periodic inspection standards will vary depending the installation environment and usage conditions. Recom-
mended maintenance periods are noted below. Keep them as reference.
To replace the cooling fan, follow the Cooling Fan Replacement on page 8-4. To replace other parts, contact
your Yaskawa representatives for technical maintenance.
Part
Cooling fan
Breaker relays
Fuses
Aluminum capacitors on PCBs
Note: The standard replacement period is based on the following usage conditions:
Ambient temperature:Yearly average of 30°C
Load factor: 80% max.
Operating rate: 12 hours max per day

Precautions when Replacing the Control Board (1PCB)

• The control board is under the bracket.
IMPORTANT
Control board
• For more information on the replacing the control board (PCB), contact your Yaskawa representative.
• For details on the how to replace the board, refer to Varispeed AC Control Board Replacement Procedure (Manual
no.: EZZ020345).
• After replacing the control board, all settings must be returned to their original default values when the product was
first shipped from Yaskawa. If the board is not reset to the defaults, the control board will fail to perform at opti-
mum levels.
Table 8.2 Part Replacement Guidelines
Standard Replacement Period
2 to 3 years
-
10 years
5 years
Control board bracket
Maintenance and Inspection
Replacement Method
Replace with new part.
Determine need by inspection.
Replace with new part.
Replace with new board.
(Determine need by inspection.)
3
8-

Hide quick links: