Consider the following properties during the configuration:
● Short-circuit voltage u
● Transformer taps for voltage adjustments:
● The voltages and insulation for the secondary-side windings must be dimensioned as
Connection
Circuit version
Infeed transformers
Recommended vector group
Drive output voltage
[kV]
3.3
The specified voltage is the required impulse withstand / test voltage for the transformer
1)
secondary windings with respect to ground. Because the transformers generally have
temperature evaluation systems in the windings, the specified test voltage is required for
strengthened insulation. If no control circuits have been installed in the windings, the test
voltage in accordance with the basic insulation is sufficient.
Basic connection
2)
Option
3)
3.5.9

Actual value acquisition

Actual current and voltage values are recorded by the AVT combination module
combination module converts analog signals into digital signals and forwards them to the PSA.
The signals are transferred to the PSA via fiber-optic cables.
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
k
2 x 2.5%.
The winding transformer taps are normally located on the primary side of the transformer.
shown in the following table:
Test voltage
[kV]
33.6
≥ 10% (in relation to 10 MVA)
Basic connection, 12-pulse infeed Series connection of the Basic Line
1 three-winding transformer
Dy5 Dd0
1)
2 x 1.7
3.5 Description of the components
Single connection
Module
2 three-winding transformers
Dy5 Dd0
with primary shift + 7.5°
Dy5 Dd0
with primary shift - 7.5°
Transformer secondary voltage
(no-load voltage)
[kV]
2 x 0.85 (2x)
2)
Description
3)
. The AVT
39