Control Settings; Table 8-2 Scaling - Siemens Sinamics GM150 6SL3835-2LN44-2AA0 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Scaling
Table 8-2
Scaling
Variable
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference control factor 100% = Maximum output voltage without
Reference flux
Reference temperature
8.3.2.2

Control settings

You can set the control keys of the AOP as desired.
1. Press the <MENU> key.
2. Press the ▲ or ▼ function key to select the <Commissioning/service> entry.
3. Press the <OK>. function key and the ▼ function key to select the <AOP settings> entry.
4. Press the ▼ function key to select the <Control settings> entry from this menu. The display
5. Press the ▲ or ▼ function key to select the desired entry. Press the <Change> function key
6. Press the <Back> function key to confirm the entries.
You can find the description and setting options for the individual menu items in the following.
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = p2003
100% = r2004
overload
100% = Rated motor flux
100% = 100° C
changes to the Control settings menu.
to change the setting.
8.3 Operation via the AOP30 operator panel
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
Operation