Operation
8.3 Operation via the AOP30 operator panel
Saving LOCAL mode
● Setting "Yes"(default setting):
● Setting "No":
Off in remote
● Setting "Yes":
● Setting "No":
The<OFF> key is always active in LOCAL mode.
LOCAL/REMOTE also during operation
● Setting "Yes":
● Setting "No" (default setting):
Red OFF key acts as
● OFF1 - Ramp-down on the deceleration ramp (p1121). OFF1 is the default setting.
● OFF2 - Immediate pulse block, motor coasts to a standstill.
● OFF3 - Ramp-down on the emergency stop ramp (p1135).
The OFF key is only effective in LOCAL mode.
Red OFF key also in REMOTE
● Setting "Yes":
● Setting "No":
In LOCAL mode, the OFF key is always in effect.
118
The LOCAL operating status is saved when the power supply is switched off and restored
the next time power is switched on.
The REMOTE operating status is activated when the supply voltage is switched back on.
It is possible to switch off in remote mode by pressing the<OFF> key.
The <OFF> key has no effect in remote operation.
You can switch between LOCAL and REMOTE when the drive is switched on (i.e. motor is
running).
Before the system switches to LOCAL, a check is carried out to determine whether the drive
is in the operational status. In this case, the system does not switch to LOCAL and outputs
the error message "Local mode during operation not possible". Before the system switches
to REMOTE, the drive is switched off and the setpoint is set to 0.
It is possible to switch off in remote mode by pressing the<OFF> key.
The <OFF> key has no effect in REMOTE operation.