Siemens Sinamics GM150 6SL3835-2LN44-2AA0 Operating And Installation Instructions page 154

Medium-voltage drive
Table of Contents

Advertisement

Operation
8.5 Functions
Additional setting parameters for analog output 0 (AO0)
Parameter
p4077[0]
Setting for the x coordinate in % of the first point on the scaling characteristic.
Parameter
p4078[0]
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used, the
unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Parameter
p4079[0]
Setting for the x coordinate in % of the second point on the scaling characteristic.
Parameter
p4080[0]
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used, the
unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Additional setting parameters for analog output 1 (AO1)
Parameter
p4077[1]
Setting for the x coordinate in % of the first point on the scaling characteristic.
154
Value
Analog outputs, characteristic value x1
Value
Analog outputs, characteristic value y1
Value
Analog outputs, characteristic value x2
Value
y2 of the characteristic of the analog out‐
puts
Value
Analog outputs, characteristic value x1
Adjustment range
-1000.00 to +1000.00%
Factory setting: 0.00 %
Adjustment range
-20.000 to +20.000 V or mA
Factory setting: 0.000 mA
Adjustment range
-1000.00 to +1000.00%
Factory setting: 100.00 %
Adjustment range
-20.000 to +20.000 V or mA
Factory setting: 20.000 mA
Adjustment range
-1000.00 to +1000.00%
Factory setting: 0.00 %
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER