IBM 3746-900 Installation And Maintenance Manual page 135

Service processor (based on 6578)
Table of Contents

Advertisement

Diagnostic Error Code
015-195-XXX
USB port Test aborted by user
015-196-XXX
USB port test halt, error threshold
exceeded
015-197-XXX
USB port test warning
015-198-XXX
USB port test aborted
015-199-XXX
USB port test failed, cause unknown
018-000-XXX
PCI Card Test Passed
018-0XX-XXX
PCI Card Failure
018-195-XXX
PCI Card Test aborted by user
018-196-XXX
PCI Card test halt, error threshold
exceeded
018-197-XXX
PCI Card test warning
018-198-XXX
PCI Card test aborted
Chapter 4. Service Processor Diagnostics and Test Information
FRU to replace/action to take
1. Information
2. Restart the test, if you need to.
1. Press F3 to review the log file. See
"Viewing the Test Log" on
page 4-8.
2. Restart the test to reset the log file.
1. Make sure that the component that
is called out is enabled or
connected.
2. Rerun the test.
3. Component that is called out in
warning statement
4. Component under test
1. If a component is called out, make
sure that it is enabled or
connected.
2. Flash the system and retest.
3. Go to "Undetermined Problems" on
page 3-22.
1. Go to "Undetermined Problems" on
page 3-22.
2. Flash the system and retest.
3. Replace component under function
test.
No action
1. PCI card
2. Riser card, if installed
3. System board
1. Information
2. Restart the test, if you need to.
1. Press F3 to review the log file. See
"Viewing the Test Log" on
page 4-8.
2. Restart the test to reset the log file.
1. Make sure that the component that
is called out is enabled or
connected.
2. Rerun the test.
3. Component that is called out in
warning statement
4. Component under test
1. If a component is called out, make
sure that it is enabled or
connected.
2. Flash the system and retest.
3. Go to "Undetermined Problems" on
page 3-22.
4-17