Technical Data - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Figure 3-24
Dimension drawing of Basic Line Filter for Smart Line Modules 55 kW, all data in mm and (inches)
3.7.6.4

Technical data

Table 3- 12
Technical data for: Basic Line Filter for Smart Line Modules
Rated power
Supply voltage:
Line voltage
Line frequency
Rated current
Power loss (see power
loss tables (Page 756))
Weight
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
6SL3000-
0HE15-0AA.
kW
5
V
3 AC 380 -10 % (-15 % < 1 min) ... 3 AC 480 +10 %
AC
Hz
47 ... 63
A
12
AC
W
20
kg
2.1
Line connection and line-side power components
0HE21-0AA.
0BE21-6DA.
10
16
25
36
20
16
2.3
5
3.7 Line filters
0BE23-6DA1
0BE25-5DA.
36
55
74
105
26
43
7.5
11.5
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents