Air-To-Water Heat Exchanger - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cooling circuit and coolant properties
13.5 Using heat exchangers
13.5.2

Air-to-water heat exchanger

If no process water is available, but it is nonetheless best to use water-cooled Line Modules,
an air-to-water cooling system can be used. The temperature of the ambient air must not be
excessively high, e.g. > 35°C (in accordance with the technical data for the air-to-water heat
exchanger).
During setup, you must ensure that a primary air cooling circuit and not a process water
circuit is installed.
Measures to prevent excessive cooling must only be taken on the secondary side by means
of closed-loop temperature control involving a thermostat or a solenoid valve.
Figure 13-5
784
Air-to-water heat exchanger
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents