NOTICE
Damage to the drive electronics when switching the line contactor under load
When switching the line contactor (type according to the recommended selection) under
load, then the contacts will be subject to premature wear. This can cause the contactor to
malfunction, with subsequent damage to the drive electronics.
• Use a leading opening auxiliary contact or use a Voltage Sensing Module (VSM10).
• If this is not possible, then avoid switching the line contactor under load.
NOTICE
Damage through use of incorrect DRIVE-CLiQ cables
Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are
used that are either incorrect or have not been approved for this purpose.
• Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the
Note
Malfunctions due to polluted DRIVE-CLiQ interfaces
Malfunctions can occur in the system through the use of polluted DRIVE-CLiQ interfaces.
• Cover unused DRIVE-CLiQ interfaces with the supplied blanking covers.
Note
Fan operation
Activation of the fan is dependent on heat sink temperature and pulse enable.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
particular application.
Line Modules Booksize Compact
5.2 Smart Line Modules Booksize Compact