Characteristics - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6SL3100-1DE22-0AA1
Cooling method
Weight
Above 40° C, a linear derating of the output current above a 26 V output voltage and higher must be observed
1)
When using circuit breakers for protection, UL approval is only possible in TN/TT line systems with grounded neutral
2)
point. Conventional fuses are required for UL approval in line supplies with grounded line conductor.
8.6.8.1

Characteristics

Derating characteristic
For ambient temperatures > 40 °C, a linear derating for the output current must be observed
as of 26 output voltage.
Figure 8-29
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Unit
Value
Internal air cooling
kg
4.8
Current derating for ambient temperatures >40 °C as a function of the output voltage
DC link components
8.6 Control Supply Module CSM