Liquid Cooled
Rated power
Electronics current drawn at 24 V DC
Total power loss
(including electronics losses, see Power loss
tables (Page 756))
DC link capacitance:
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker (IEC 60947 and UL)
Rated short-circuit current SCCR
Max. total cable length
4)
Rated flow rate for water
at 70 kPa pressure drop (for other coolants,
see Cooling circuit and coolant properties
(Page 771)
Volume of liquid internal
Max. coolant temperature
without derating
with derating
Max. permissible heat sink temperature
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
4)
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
kW
A
DC
W
μF
μF
cos φ
kA
3)
l/min
ml
° C
° C
° C
kg
4.6 Active Line Modules Liquid Cooled
6SL3135-7TE31-2AA3
120
1.8
2243.2
3995
20000
1
See Chapter Overcurrent protection using fuses and
circuit breakers (Page 51)
65
See Chapter Combination options, Line Modules with line
reactors and line filters (Page 135)
8
100
45
50
80
23
Line Modules Booksize