Siemens SINAMICS S120 Manual page 295

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

16 kW to 55 kW Smart Line Modules
Table 4- 78
X21 EP terminal / temperature sensor for 16 kW to 55 kW Smart Line Modules
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 730)
The temperature sensor type and the temperature output can be selected by parameter (see the SINAMICS S120/S150
1)
List Manual).
Temperatures are sensed, but are not evaluated in the Smart Line Module.
Terminals X21.1 and X21.2 - temperature sensor connection
Danger to life due to electric shock in the event of voltage flashovers on the temperature
sensor cable
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of protective
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
NOTICE
Damage to motor in the event of incorrectly connected KTY temperature sensor
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating can cause damage to the motor.
• Connect the KTY temperature sensor with the correct polarity.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Function
+ Temp
- Temp
EP +24 V (pulse enable)
EP M (Enable Pulses)
WARNING
separation.
motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal
Module TM120.
4.10 Smart Line Modules with external air cooling
Technical data
Temperature sensors
: KTY84–1C130 / PT1000 / PTC /
1)
bimetallic switch with NC contact
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption, typical: 4 mA at 24 V
Isolated input
Line Modules Booksize
295

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents