Line Modules Booksize
4.4 Active Line Modules with external air cooling
4.4.2.3

X12 fan connection

Active Line Modules 80 kW and 120 kW are equipped with an interface for connecting the
sub-chassis fan. The interface is located on the underside of the Line Module.
Table 4- 14
X12 fan connection
Terminal
1
2
4.4.2.4

X21 EP terminals

Table 4- 15
X21 EP terminal / temperature sensor
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 730)
The temperature sensor type and the temperature output can be selected by parameter (see the SINAMICS S120/S150
1)
List Manual).
Temperatures are detected but not evaluated in the Active Line Module.
2)
Terminals X21.1 and X21.2
When using an Active Interface Module, its temperature output must be connected at
terminals X21.1 and X21.2.
176
Function
Fan connection +
Fan connection -
Designation
+ Temp
- Temp
EP +24 V (pulse enable)
EP M (Enable Pulses)
Technical data
Voltage 48 V DC for the supplied fan
Technical data
Temperature sensors
: KTY84–1C130
1)
PTC
/bimetallic switch with NC contact
2)
If an Active Interface Module is used, the temperature
input must be connected to the Active Interface Module
sensor (bimetallic switch with NC contact).
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption, typical: 4 mA at 24 V
Isolated input