1.3

Technical specifications

Technical data
Unless explicitly specified otherwise, the following technical data are valid for all the following
components of the SINAMICS S120 Liquid Cooled drive system.
Table 1- 1
General technical data
Electrical data
Line supply voltage
Line frequency
Output voltage
Output frequency
Electronic power supply
Rated short-circuit current SCCR (Short
Circuit Current Rating)) in accordance
with UL508C (up to 600 V), in conjunction
with the specified fuses or circuit-breakers
Frequency with which the DC link is
precharged
Interference suppression
Overvoltage category
Mechanical data
Vibratory load
Transport
1)
Operation
Shock stressing
Transport
1)
Operation
Ambient conditions
Degree of protection
Protection class
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
380 V 3 AC -10% (-15% < 1 min) to 480 V 3 AC +10%
500 V 3 AC -10% (-15% < 1 min) to 690 V 3 AC +10%
47 Hz to 63 Hz
0 to line connection voltage, depending on the type of infeed.
With an Active Line Module, it is also possible to achieve a higher output
voltage.
Vector control: 0 Hz to 600 Hz
Servo control: 0 Hz to 650 Hz
U/f control: 0 Hz to 650 Hz
24 V DC (20.4 V - 28.8 V)
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = Negative polarity grounded via the electronics
1.1 kW – 447 kW: 65 kA
448 kW – 671 kW: 84 kA
672 kW – 1193 kW: 170 kA
>1194 kW: 200 kA
Max. 1 precharge every 3 minutes
Category C3 (second environment) to EN 61800-3
Class III to EN 61800-5-1
EN 60721-3-2, class 2M2
Test values in accordance with EN 60068-2-6 test Fc:
10 to 58 Hz with constant deflection = 0.075 mm
58 to 150 Hz with constant acceleration = 9.81 m/s² (1 g)
EN 60721-3-2, class 2M2
Test values in accordance with EN 60068-2-27 test Ea: 98 m/s² (10 g) /
20 ms
IP00 acc. to EN 60529
Class I (with protective conductor system) and class III (PELV) to
EN 61800-5-1