1.3
Technical specifications
Technical data
Unless explicitly specified otherwise, the following technical data are valid for all the following
components of the SINAMICS S120 Liquid Cooled drive system.
Table 1- 1
General technical data
Electrical data
Line supply voltage
Line frequency
Output voltage
Output frequency
Electronic power supply
Rated short-circuit current SCCR (Short
Circuit Current Rating)) in accordance
with UL508C (up to 600 V), in conjunction
with the specified fuses or circuit-breakers
Frequency with which the DC link is
precharged
Interference suppression
Overvoltage category
Mechanical data
Vibratory load
Transport
•
1)
Operation
•
Shock stressing
Transport
•
1)
Operation
•
Ambient conditions
Degree of protection
Protection class
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
380 V 3 AC -10% (-15% < 1 min) to 480 V 3 AC +10%
•
500 V 3 AC -10% (-15% < 1 min) to 690 V 3 AC +10%
•
47 Hz to 63 Hz
0 to line connection voltage, depending on the type of infeed.
With an Active Line Module, it is also possible to achieve a higher output
voltage.
Vector control: 0 Hz to 600 Hz
Servo control: 0 Hz to 650 Hz
U/f control: 0 Hz to 650 Hz
24 V DC (20.4 V - 28.8 V)
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = Negative polarity grounded via the electronics
1.1 kW – 447 kW: 65 kA
•
448 kW – 671 kW: 84 kA
•
672 kW – 1193 kW: 170 kA
•
>1194 kW: 200 kA
•
Max. 1 precharge every 3 minutes
Category C3 (second environment) to EN 61800-3
Class III to EN 61800-5-1
EN 60721-3-2, class 2M2
•
Test values in accordance with EN 60068-2-6 test Fc:
•
–
10 to 58 Hz with constant deflection = 0.075 mm
–
58 to 150 Hz with constant acceleration = 9.81 m/s² (1 g)
EN 60721-3-2, class 2M2
•
Test values in accordance with EN 60068-2-27 test Ea: 98 m/s² (10 g) /
•
20 ms
IP00 acc. to EN 60529
Class I (with protective conductor system) and class III (PELV) to
EN 61800-5-1
System overview
1.3 Technical specifications
23