Danger to life due to electric shock and fire hazard caused by overcurrent protective
equipment tripping too late
Overcurrent protective equipment that trips too late or not all can cause electric shock or
fire.
• To protect personnel and for fire protection purposes, at the infeed point, the short-
Danger to life through electric shock due to incorrect connection to the DC link
Incorrect connections can lead to overheating and therefore a risk of fire. There is also a
risk of an electric shock. This can result in serious injury or death.
• Only use adapters (DC link adapters and DC link rectifier adapters) released by
Danger to life through electric shock due to missing DC link side covers
There is a danger of an electric shock through contact when the side covers of the DC link
are missing.
• Mount the side covers on the first and last component in the drive line-up.
• Order any missing side covers (Article number: 6SL3162-5AA00-0AA0).
Danger to life caused by high leakage currents when the protective conductor in the line
feeder cable is interrupted
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Carefully comply with the applicable regulations for dimensioning the protective
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
WARNING
circuit rating and loop impedance must match the specifications in the documentation so
that the installed overcurrent protection devices trip within the specified time.
WARNING
Siemens for the connection to the DC link.
WARNING
WARNING
conductor (see Chapter "Protective connection and equipotential bonding (Page 736)").
Line Modules Booksize Compact
5.2 Smart Line Modules Booksize Compact