Motor Modules Booksize
6.3 Motor Module with external air cooling
Insert plate
Mounting plate
Cover
Rear panel
Air discharge
Air inlet - filter with filter fan
To comply with degree of protection IP54, the surfaces
be sealed all round the circumference (e.g. Terostat-91 sealant from the Teroson company).
Figure 6-44
Example 2: mounting in the cabinet with mounting plate
It is recommended that you attach a cover and filter fan to the cabinet.
The filtered fan must be fitted in such a way that the cooling air required by the drive line-up
is not restricted. The overall cooling air requirement is obtained from the sum of the
individual components (see Chapter Technical data (Page 403)).
402
Setween the mount ing plate and the cabinet strip must
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8