Motor Modules Booksize
6.3 Motor Module with external air cooling
①
Insert plate
②
Mounting plate
③
Cover
④
Rear panel
⑤
Air discharge
⑥
Air inlet - filter with filter fan
⑦
To comply with degree of protection IP54, the surfaces
be sealed all round the circumference (e.g. Terostat-91 sealant from the Teroson company).
Figure 6-44
Example 2: mounting in the cabinet with mounting plate
It is recommended that you attach a cover and filter fan to the cabinet.
The filtered fan must be fitted in such a way that the cooling air required by the drive line-up
is not restricted. The overall cooling air requirement is obtained from the sum of the
individual components (see Chapter Technical data (Page 403)).
402
⑥
Setween the mount ing plate and the cabinet strip must
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Booksize Power Units