X22 Digital Inputs - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
4.9 Smart Line Modules with internal air cooling
Terminals X21.3 and X21.4
For operation, the 24 V DC voltage must be connected to terminal X21.3 and ground to
terminal X21.4.
Pulse cancellation is activated if the power supply is disconnected. As a consequence,
regenerative feedback is deactivated and the bypass relay drops out. If the Line Module is
not disconnected from the line supply when the EP terminal is de-energized, for example,
because a line contactor is not installed, then the DC link remains charged.
NOTICE
Damage to the drive electronics when switching the line contactor under load
When switching the line contactor (type according to the recommended selection) under
load, then the contacts will be subject to premature wear. This can cause the contactor to
malfunction, with subsequent damage to the drive electronics.
• Use a leading opening auxiliary contact or use a Voltage Sensing Module (VSM10).
• If this is not possible, then avoid switching the line contactor under load.
4.9.4.4

X22 digital inputs

Table 4- 68
X22 digital inputs for Smart Line Modules 5 kW and 10 kW
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 730)
DI: Digital input
1)
272
Designation
1)
24 V power supply
DI: Disable Regeneration
DI: Reset
Ground
Technical data
Electronics power supply for controlling digital inputs
X22.2 and 3
Deactivate regenerative feedback (high active)
No power is supplied back to the network from the DC
link. The regenerative energy of the motors may have to
be reduced using a combination of the Braking Module
and braking resistor.
Reset faults (negative edge)
Electronics ground
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8