Line Modules Booksize
4.8 Basic Line Modules with cold plate
4.8.6

Mounting

Please note the following before mounting a Basic Line Module with cold plate onto a
customer-specific heat sink:
● Before mounting, check the surface of the heat sink to ensure that it is not damaged.
● To improve heat transfer, a heat-conducting medium must be used. Special spherical-
indented heat-conducting foil must be used for this purpose. Every Basic Line Module
cold plate is supplied with heat-conducting foil cut to the right size. Note the mounting
position of the heat-conducting foil (see figures below).
Note
• Also replace the heat-conducting foil when replacing a component.
• Only use heat-conducting foil released or supplied by Siemens.
Table 4- 61
Heat-conducting foil, 100 mm
Heat-conducting foil, 150 mm
Heat-conducting foil, 200 mm
Note
To mount the components, M6 threaded bolts and hexagon nuts/grub screws ISO 7436-
M6x40-14 H, property class 8.8 are recommended.
254
Overview of heat-conducting foils
Article No.
6SL3162-6FD00-0AA0
6SL3162-6FF00-0AA0
6SL3162-6FH00-0AA0
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8