DC link components
8.3 Braking Module Booksize Compact
Special points to note in relation to mounting on a cold plate
To improve heat transfer, a heat-conducting medium must be used. Special spherical-
indented heat-conducting foil must be used for this purpose. Every Braking Module Booksize
Compact is supplied with heat-conducting foil cut to the right size. Note the mounting
position of the heat-conducting foil.
Note
• Also replace the heat-conducting foil when replacing a component.
• Only use heat-conducting foil released or supplied by Siemens.
Heat-conducting foil, 50 mm
8.3.8

Technical specifications

Table 8- 14
Technical data
6SL3400-1AE31-0AA.
Line supply
DC link voltage
ON threshold
Braking power
Maximum
1)
Continuous braking power
Electronics power supply
Electronics current consumption (at DC 24 V)
Standby
mode
Current carrying capacity:
DC link busbars
24 V busbar
Power loss (see power loss tables (Page 756))
Standby
operation
Switching frequency
Cooling methods
Max. ambient temperature
Weight
At the upper switch-on threshold
1)
514
Article No.
6SL3162-6FB01-0AA0
200 V
V
250 ... 360
DC
V
DC
kW
kW
V
DC
A
DC
A
DC
A
DC
A
DC
W
W
Hz
° C
kg
400
50
2.5
24 (20.4 ... 28.8)
0.2
0.4
100
20
5
25
2000
Internal air cooling
Cold plate cooling
55
2.7
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
400 V
510 ... 720
760
100
5
Booksize Power Units