System overview
2.5 System data
Shock test in operation
Installation altitude
Operation
Permissible cooling medium tem-
perature (air) and installation alti-
tude in operation
Product packaging (storage packaging) is individual packaging for storage - and does not satisfy the requirements for
1)
transport. As a consequence, product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport - or secondary packaging, which together
2)
with the product packaging, satisfies the requirements for transport.
Table 2- 5
Certificates
Declarations of Conformity
Approvals
1)
Possible deviations are specified for the corresponding component.
1)
48
According to IEC 60068-2-27 test Ea (half-sine)
0 ... 1000 m above sea level without derating
> 1000 ... 4000 m
Reduction of the output current by 10 % per 1000 meters, or
Reduction in the ambient temperature by 5°C per 1000 meters
> 2000 ... 4000 m
Operation on line supply systems with grounded neutral point, or
Operation on an isolating transformer with secondary grounded neutral point
0 °C ... +40 °C and an installation altitude of up to 1000 m without derating,
>40° C to +55 °C: Reduction of the output current by 2.67 % pro °C
Installation altitude > 1000 ... 4000 m: Reduction in the ambient temperature by 3.5°C
per 500 m.
CE
cULus
cURus
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8