Advertisement

No.
Name
b1-16
Run Command Selection 2
b1-17
Run Command at Power Up
<11> Setting 2 and 3 are not available when using CLV.
b2: DC Injection Braking and Short Circuit Braking
No.
Name
DC Injection Braking Start
b2-01
Frequency
DC Injection Braking
b2-02
Current
DC Injection Braking Time
b2-03
at Start
DC Injection Braking Time
b2-04
at Stop
Magnetic Flux Compensation
b2-08
Value
Short Circuit Brake Time at
b2-12
Start
Short Circuit Brake Time at
b2-13
Stop
b2-18
Short Circuit Braking Current
<7> A coasting motor may require a braking resistor circuit to bring the motor to a stop in the required time.
<10> Default setting is determined by the control mode (A1-02).
b3: Speed Search
No.
Name
Speed Search Selection at
b3-01
Start
Speed Search Deactivation
b3-02
Current
Speed Search Deceleration
b3-03
Time
b3-04
V/f Gain during Speed Search
b3-05
Speed Search Delay Time
Output Current 1 during
b3-06
Speed Search
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Enabled when a terminal set for "External reference" (H1-
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
0: Disregarded. A new Run command needs to be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command is
already enabled.
Sets the frequency at which DC Injection Braking starts when "Ramp to stop"
(b1-03 = 0) is selected.
Sets the DC Injection Braking current as a percentage of the drive rated current.
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and
CLV/PM) time at start. Disabled when set to 0.00 s.
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and
CLV/PM) at stop.
Sets the magnetic flux compensation as a percentage of the no-load current
value (E2-03).
Sets the time for Short Circuit Braking operation at start.
Sets the Short Circuit Braking operation time at stop.
Determines the current level for Short Circuit Braking. Set as a percentage of the
motor rated current.
0: Disabled
1: Enabled
Sets the current level at which the speed is assumed to be detected and Speed
Search is ended. Set as a percentage of the drive rated current.
Sets output frequency reduction time during Speed Search.
Determines how much to lower the V/f ratio during Speed Search.
Output voltage during Speed Search equals the V/f setting multiplied by b3-04.
When using an external contactor on the output side, b3-05 delays executing
Speed Search after a momentary power loss to allow time for the contactor to
close.
Sets the current injected to the motor at the beginning of Speed Estimation
Speed Search. Set as a coefficient for the motor rated current.
Description
= 2) closes.
Description
<7>
<7>
Description
B Parameter List
Setting
Default: 0
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Setting
Default:
<10>
Min: 0.0 Hz
Max: 10.0 Hz
Default: 50%
Min: 0%
Max: 100%
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
Default:
<10>
Min: 0.00 s
Max: 10.00 s
Default: 0%
Min: 0%
Max: 1000%
Default: 0.00 s
Min: 0.00 s
Max: 25.50 s
Default: 0.50 s
Min: 0.00 s
Max: 25.50 s
Default: 100.0%
Min: 0.0%
Max: 200.0%
Setting
Default:
<10>
Min: 0
Max: 1
Default:
<10>
Min: 0%
Max: 200%
Default: 2.0 s
Min: 0.1 s
Max: 10.0 s
Default:
<9>
Min: 10%
Max: 100%
Default: 0.2 s
Min: 0.0 s
Max: 100.0 s
Default:
<9>
Min: 0.0
Max: 2.0
B
133