Setting 3: User-set speed agree 1 (f
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the
speed agree width (L4-02) of the programmed speed agree level (L4-01).
Status
Open
Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 70
Output Frequency
Frequency
reference
User Set
Speed Agree 1
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
H3-01
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and
bias settings will be simply read as 0%.
Setting 1: –10 to 10 Vdc
The input level is –10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then
the motor will rotate in reverse.
H3-02: Terminal A1 Function Selection
Determines the function assigned to analog input terminal A1.
No.
H3-02
H3-03, H3-04: Terminal A1 Gain and Bias Settings
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Both can be used to adjust the characteristics of the analog input signal to terminal A1.
No.
H3-03
H3-04
Setting Examples
• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency
reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will
be equal to E1-04 above 5 Vdc.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
/f
Agree 1)
ref
set
or Motor Speed
OFF
ON
Figure 70 User Set Speed Agree 1 Time Chart
Name
Terminal A1 Signal Level Selection
Name
Terminal A1 Function Selection
Name
Terminal A1 Gain Setting
Terminal A1 Bias Setting
4 Start-Up Programming & Operation
Description
L4-01
Output
frequency
+/- L4-02
Frequency
reference
ON
OFF
L4-01
+/- L4-02
Setting Range
0 to 1
Setting Range
0 to 31
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Default
0
Default
0
Default
4
100.0%
0.0%
83