i Preface & General Safety
Selecting a Circuit Breaker or Leakage Circuit Breaker
Yaskawa recommends installing Earth Leakage Circuit Breaker (ELCB) to the power supply side. The ELCB should be
designed for use with an AC drive (e.g. Type B according to IEC 60755).
Select a MCCB (Molded Case Circuit Breaker) or ELCB with a rated current that is 1.5 to 2 times higher than the rated
current of the drive in order to avoid nuisance trips caused by harmonics in the drive input current.
Magnetic Contactor Installation
Use a magnetic contactor (MC) to ensure that power to the drive can be completely shut off when necessary. The MC
should be wired so that it opens when a fault output terminal is triggered.
Avoid switching a magnetic contactor on the power supply side more frequently than once every 30 minutes. Frequent
switching can cause damage to the drive.
Inspection and Maintenance
Capacitors in the drive take time to discharge even after the power has been shut off. After shutting off the power, wait
for at least the amount of time specified on the drive before touching any components.
The heatsink can become quite hot during operation, and proper precautions should be taken to prevent burns. When
replacing the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down.
Even when the power has been shut off for a drive running a PM motor, voltage continues to be generated at the motor
terminals while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
• Applications where the machine can still rotate even though the drive has fully stopped should have a load switch
installed to the output side of the drive. Yaskawa recommends manual load switches from the AICUT LB Series by
AICHI Electric Works Co., Ltd.
• Do not allow an external force to rotate the motor beyond the maximum allowable speed, also when the drive has been
shut off.
• Wait for at least the time specified on the warning label after opening the load switch on the output side before
inspecting the drive or performing any maintenance.
• Do not open and close the load switch while the motor is running, as this can damage the drive.
• If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped
before closing the load switch.
Wiring
All wire ends should use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal
manufacturer for crimping.
Transporting the Drive
Never steam clean the drive.
During transport, keep the drive from coming into contact with salts, fluorine, bromine, phthalate ester, and other such
harmful chemicals.
Notes on Motor Operation
Using a Standard Motor
Low Speed Range
The cooling fan of a standard motor is usually designed to sufficiently cool the motor at the rated speed. As the self-
cooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the
motor. To prevent motor damage from overheat, reduce the load torque as the motor slows.
Figure 2
shows the allowable load characteristics for a Yaskawa standard motor. A motor designed specifically for
operation with a drive should be used when 100% continuous torque is needed at low speeds.
12
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide