3 Electrical Installation
Model
Terminal
CIMR-A
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0088
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0103
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0139
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0165
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0208
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
4A0250
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
–, +1
4A0296
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
–, +1
4A0362
+3
40
For Asia
<1>
Recommended
Applicable
Gauge
Gauge
mm
mm
2
2
30
22 to 50
30
22 to 50
38
30 to 50
22
14 to 50
22
14 to 22
38
30 to 50
38
30 to 50
60
30 to 50
30
22 to 50
22
14 to 22
60
38 to 100
60
50 to 100
100
60 to 100
50
30 to 100
22
22
80
60 to 100
80
80 to 100
50 × 2P
50 to 100
60
50 to 100
22
22 to 30
150
30 to 150
150
30 to 150
80 × 2P
38 to 150
80
22 to 80
22
22 to 150
150
38 to 325
150
38 to 325
200
80 to 325
125
38 to 325
22
22 to 200
200
80 to 325
200
80 to 325
325
80 to 325
150
38 to 325
30
30 to 200
250
80 to 325
250
80 to 325
325
100 to 325
200
80 to 325
30
30 to 200
For U.S.A
<2>
Recommended
Applicable
Gauge
Gauge
AWG, kcmil
AWG, kcmil
2
3 to 1/0
2
3 to 1/0
–
3 to 1/0
–
6 to 1/0
4
6 to 4
1/0
2 to 1/0
1
2 to 1/0
–
3 to 1/0
–
4 to 1/0
4
6 to 4
3/0
1/0 to 4/0
2/0
1/0 to 4/0
–
1/0 to 4/0
–
3 to 4/0
4
4
4/0
3/0 to 4/0
4/0
3/0 to 4/0
–
1 to 4/0
–
1/0 to 4/0
4
4 to 2
300
2 to 300
300
2 to 300
–
1 to 250
–
3 to 3/0
4
4 to 300
400
1 to 600
400
1/0 to 600
–
3/0 to 600
–
1 to 325
2
2 to 350
500
2/0 to 600
500
2/0 to 600
–
3/0 to 600
–
1 to 325
2
2 to 350
4/0 × 2P
3/0 to 600
4/0 × 2P
3/0 to 600
–
4/0 to 600
–
3/0 to 600
1
1 to 350
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
For Europe and China
<3>
Recommended
Applicable
Gauge
Gauge
mm
mm
2
2
25
16 to 50
25
25 to 50
–
25 to 50
–
16 to 50
16
16 to 25
35
25 to 50
35
25 to 50
–
25 to 50
–
25 to 50
16
16 to 25
50
35 to 95
50
35 to 95
–
50 to 95
–
25 to 95
25
25
70
50 to 95
70
70 to 95
–
35 to 95
–
50 to 95
35
25 to 35
95
35 to 95
95
35 to 95
–
35 to 150
–
25 to 70
50
50 to 150
120
95 to 300
120
95 to 300
–
70 to 300
–
35 to 300
70
70 to 240
185
95 to 300
185
95 to 300
–
70 to 300
–
35 to 300
95
95 to 240
240
95 to 300
240
95 to 300
–
95 to 300
–
70 to 300
120
120 to 240
Tightening
Screw
Torque
Size
N m (lb.in.)
9 to 11
M8
(79.7 to 97.4)
9 to 11
M8
(79.7 to 97.4)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)