4.1.1.3 Shield connection rail

Figure 8:
For EMC conform installation of the power cables an shield connection rail is available as
option. Commercially available shield connection clamps for rails 3x10 mm can be used. Die
Shield connection clamps (screw or spring type) must match the to cable diameter and are
therefore not included.
4.2

Power unit

4.2.1

Description of the terminal blocks

4.2.1.1 Terminal block X1A

Terminals
L1, L2, L3
H1, H2
RB+, RB-
PE,
Figure 9:
All SubD connectors have screw sockets with UNC 4-40 thread (tight-
ening torque 0.4 Nm).
Shield connection rails 3 x 10 mm are available for strain relief / shield
connection of the control cables. Commercially available shield con-
nection clamps (screw- or spring type) of suitable size or cable ties can
be used on them.
Shield connection rail (Mat.Nr. 00P6ZGG-0002)
Function
Mains input 3-phase
Heater input 400 Vac (op-
tion)
external braking resistor
(option)
protection-/functional earth
Terminal strip X1A
Power unit
Permissible cable
cross section [mm²]
0,75...16
0,25...6
0,75...16
4x M6; Depth of thread 10 mm;
Tightening torque 4.8 Nm
Strip length
[mm]
18
15
18
25