Chapter 4 - System Mechanical Installation - Honeywell Touchpoint Plus Wireless Technical Handbook

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

MAN0984_Iss 2_09/19
3020M5001_2
System Mechanical Installation
Chapter 4 – System Mechanical Installation
The system can be directly wall-mounted, mounted on an optional mounting fixture. Whichever method is
chosen, the mounting must be sound, secure, and capable of supporting the weight of the enclosure plus the
weight of any cables and glands.
When choosing a location, it must be easily visible and accessible, with room to mount an external power
isolator. There must also be room to fully open the access door, which opens to the left, and room to easily
access the door locking handle and its securing screws, which are situated on the right.
The units should be mounted so that the screen can be easily accessed and seen, but they should not
obstruct accesses, walkways or exits.
Although the units are IP65 when installed correctly, they should be mounted away from heat sources, out of
direct sunshine, and should be protected from rain, severe weather, steam or excess humidity and
condensation.
These units have only passive cooling, so an adequate airflow must be maintained to prevent overheating.
Assembly
Wall mounted cabinet
It is the Customer's responsibility to ensure that the equipment is correctly installed, and that cable entry glands
Failure to do so will invalidate the quoted IP / NEMA / Pollution ratings and may invalidate the warranty.
The units as supplied have two hex-socket securing screws in the access door handle, and these have to be
undone prior to opening the handle. Failing to do so could cause irreparable damage to the housing.
The handle must be correctly locked and the screws must be correctly tightened when the unit is in operation.
IP
Pollution Degree
65
or blanks of the appropriate IP rating are correctly used.
Failing to fully secure the enclosure is unsafe and will invalidate product certification.
When properly installed using the
2
appropriate cable entry glands
CAUTION
CAUTION
18
Touchpoint Plus Wireless
Technical Handbook
Remarks

Advertisement

Table of Contents
loading

Table of Contents