MAN0984_Iss 2_09/19
3020M5001_2
Module
Name
Relay
Channel Tag
Output
Relay
Normal State
Output
Relay
Alarm Update Function
Output
Relay
Active Delay Time
Output
Relay
Relay Hold Time
Output
Relay
Relay Latch
Output
Relay
Event Type
Output
Relay
Event Source Type
Output
Relay
Gas Index
Output
Relay
Vote Count
Output
Relay
Reserved
Output
Module
Name
WIO
Channel Enable
Module
Configurable Parameter Reference Guide
Description
25 characters
Energized/ De-energized
If enabled, only unacknowledged
alarm conditions will be
considered during C&E evaluation for
this output channel.
An alarm acknowledgement will reset
a relay output that
is configured for alarm update
function.
However if the alarm update is NOT
enabled the relay
contact will only be reset if the alarm
is reset.
Delay time to activate the relay
Delay time to de-activate the relay
Relay Latch
Event type - Alarm, Fault, Warning,
Inhibit
Detector, Sensor, WindSensor
Gas index number of wireless
detector
Occurred event count. Only to use to
detector type
Description
Channel Enable/Disable
Read/
Range
Write
Alphanumeric Character
R/W
Range
Energized/ De-
R/W
energized
R/W
Enable/ Disable
R/W
0~3000
R/W
0~3000
R/W
Enable/ Disable
Alarms, Fault, Inhibit,
R/W
Warning
R/W
0~2
R/W
1~76
R/W
1~255
R/W
0
Read/
Range
Write
R
Disable/Enable
102
Default
Remark
Value
50 chars
Energized
0
Disable
0
0 sec
Second
0 sec
Second
Disable
0
Alarm1(1), Alarm2(2), Alarm3(3), Fault(4), Inhibit(5),
Warning(6)
Detector(0), Sensor(1), WindSensor(2)
1~76
1
1~255
0
0
Default
Remark
Value
Disable
0
Touchpoint Plus Wireless
Technical Handbook