Faults And Warnings; View Faults And Warnings; Acknowledging An Active Fault Or Warning; Reset A Latched Fault Or Warning - Honeywell Touchpoint Plus Wireless Technical Handbook

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

MAN0984_Iss 2_09/19
3020M5001_2

6.7 Faults and Warnings

6.7.1 View Faults and Warnings

Detailed information about active Faults and Warnings can be viewed:
1) From the Input and output screen, select either the Fault (yellow filter) icon, or the Warning (blue filter)
icon. The screen will show a filtered list of only the active Faults or Warnings.
Wireless node disconnections are not fault until online monitor fault
count)

6.7.2 Acknowledging an Active Fault or Warning

Note: Operator or higher level access is required
Note: Accept and Acknowledge have the same meaning in this context.
An active fault or warning can be acknowledged by touching the Accept button for >1 second. This will
acknowledge ALL active events and the channel LED and icon will stop flashing.

6.7.3 Reset a Latched Fault or Warning

Note: Operator or higher access level is required.
A latched fault or warning can be reset in three ways by:
1) Touching the Reset button for >3 seconds. This will reset ALL latched alarms, faults and warnings,
provided that the event has cleared. It will also reset any latched relay outputs.
2) Selecting Menu > Maintenance > Reset alarms/faults. This will reset all latched events for the channel,
provided that the input signal has returned to Normal / within tolerance.
3) Remote reset input.