Honeywell Touchpoint Plus Wireless Technical Handbook page 114

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

MAN0984_Iss 2_09/19
3020M5001_2
Parameter Name
Min Range
Resolution
Sensor Name
Signal Fault Max
Signal Fault Min
Signal Inhibit Max
Signal Inhibit Min
Signal Over Range Limit
Signal Under Range Limit
Signal Warning Max
Signal Warning Min
Span Calibration Conc.
STEL Interval
TWA Interval
Configurable Parameter Reference Guide
Parameter Description
Minimum configurable measuring range
Note: wireless detectors are fixed and only trend range can be
changed.
Index of display resolution for gas relevant parameters
Sensor name consists of gas name, full scale range and
measurement unit
Upper mA input signal range to detect the fault reported by the
detector
Lower mA input signal range to detect the fault reported by the
detector
Upper mA input signal range to detect whether detector is inhibited or
not
Lower mA input signal range to detect whether detector is inhibited or
not
Upper allowable limit for the input signal from the sensor/detector. If
the signal is out of this limit, the I/O board will generate an input
signal fault
Lower allowable limit for the input signal from the sensor/detector. If
the signal is out of this limit, the I/O board will generate an input
signal fault
Upper mA input signal range to detect remote warning from the
detector
Lower mA input signal range to detect remote warning from the
detector
Target span gas concentration. Normally it is 50 %FSD
STEL period in minutes. The catalogue is using index instead.
TWA period in hours. The catalogue is using index instead.
Applies to
All
All
All
mA sensor
only
mA sensor
only
mA sensor
only
mA sensor
only
All
All
mA sensor
only
mA sensor
only
All
mA sensor
only
mA sensor
only
108
Touchpoint Plus Wireless
Default
Measurement
Read/Write
Value
units
R
conc.
RW
per target gas
n/a
R
per target gas
n/a
RW
1.1
mA
RW
0
mA
RW
2.2
mA
RW
1.8
mA
RW
22
mA
RW
100 %FSD
mA
RW
0
mA
RW
0
mA
RW
50 %FSD
conc.
RW
15
minutes
RW
8
hours