How To Replace A Faulty I/O Module - Honeywell Touchpoint Plus Wireless Technical Handbook

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

MAN0984_Iss 2_09/19
3020M5001_2

8.3 How to Replace a Faulty I/O Module

A faulty I/O module can be replaced with another of the same type, without needing to reprogram the
configuration. Touchpoint Plus Wireless will automatically copy over the configuration to the new module.
If the relays are switching mains voltages, hazardous live terminals may be present within the
Note: Service or higher level access is required
Note: The new module must be the same type with same number of inputs/outputs as the old module.
1) Switch off the Touchpoint Plus Wireless (Menu > Maintenance > Power off)
2) Isolate the power supplies and switch off the battery if there is a back-up battery installed
3) Disconnect the faulty module
4) Replace the module
Note: Not required for WIO Module.
5) Reconnect the module
6) Switch on the battery if there is a back-up battery installed and switch on the Touchpoint Plus Wireless
7) Login as an Administrator
8) Select Menu > Configuration > HW Module Control Panel
9) In the Board Control panel, select the empty blue block corresponding to the replaced module and touch
'Replace'
Maintenance
Relay Output Module even if the Touchpoint Plus system is isolated.
Ensure that all current is isolated and dissipated before touching live terminals.
ANTI–STATIC PRECAUTIONS
Antistatic Precautions are required to prevent severe damage to electronic components.
WARNING
79
Touchpoint Plus Wireless
Technical Handbook

Advertisement