MAN0984_Iss 2_09/19
3020M5001_2
IO Module color:
Gray: The module cannot be added, removed or replaced because the module is mandatory.
Yellow:
Module was added previously but no module is detected now (removed).
Sky blue:
Serial number or module type does not match (IO Module is replaced).
Background color: Installed.

8.4 How to Add a New I/O Module

The Touchpoint Plus Wireless system can easily be expanded by adding new I/O modules.
Note: Service or higher level access is required
Note: A module which has previously been configured in one system cannot be added to another system,
unless it was correctly removed from the original system's configuration.
1) Switch off the Touchpoint Plus Wireless (Select Menu > Maintenance > Power off )
2) Isolate power supplies
3) Fit the new module of the required type to an empty slot, ensuring that that the module is the correct way
up and with the label towards you
4) Electrically connect the new module
5) Switch on the Touchpoint Plus Wireless
6) Login as an administrator
7) Select the Menu > Configuration > Module Control Panel
8) Select an empty block corresponding to the new module and touch 'Add'
9) Commission each channel in turn
Note: See Ch.7 Commissioning for detailed instructions for further information.